ORS 142 ECOv

 

ORS 142 ceiling-mounted smoke switch

  • with optional line monitoring as per DIN EN 14637
  • Smoke detection: as per EN 54, part 7, 
  • Temperature: 70 °C 
  • Operating voltage: 18-28 V DC
  • Current consumption: at 28 V DC, quiescent 22 mA, alarm 11 mA, fault 16 mA,
  • Relay contact: Opener
  • Protection class: IP 42
  • Temperature range: -20°C to +60°C
    Materials
    Standards
    Product information